DIY HVAC Tools

Heil mini split error code PF

Drive board ambient temperature sensor error.

  • TypeFault
  • SystemTemperature sensor
  • Can I fix it?Homeowner checks, then maybe a tech
  • Applies toDLC4 / DLF4 series, 2013 to 2015 (Gree-built)

What PF means on a Heil

The control board is reading the drive board ambient temperature sensor as open or shorted, which means the thermistor (a small resistor whose resistance changes with temperature) is returning a value outside its normal range. The unit usually stops, or runs with the wrong output, because the control board no longer trusts that temperature reading.

On this platform, PF is a fault: something has failed or is disconnected and needs diagnosis.

Common causes

  • The drive board ambient temperature thermistor has failed (they do drift and fail with age and heat cycling).
  • Its plug has worked loose from the control board, or a pin has corroded.
  • The sensor lead is chafed, pinched or chewed, giving an intermittent open or short.
  • The control board's sensor input has failed (rare compared with the sensor itself).

How to fix it yourself

Work through the checks below first; they resolve most cases. If they do not, the repair itself may need a technician.

  1. Reset the system: switch the breaker (or the outdoor disconnect) off, wait a full five minutes so the boards fully discharge, then switch it back on and restart from the remote.
  2. If the code comes straight back after a reset, the fault is real and not a glitch.
  3. With power off, locate the drive board ambient temperature sensor on the compressor drive board. Follow its lead back to the board and reseat the plug firmly.
  4. Inspect the lead for damage along its whole length, especially where it passes through the chassis.
  5. If you have a multimeter, unplug the sensor and measure its resistance. A reading near zero ohms (short) or infinite (open) confirms a bad sensor. Most mini split thermistors read roughly 5 to 20 kΩ at room temperature, so a value in that range with a steady drift as you warm it in your hand means the sensor is fine and the board is the suspect.
  6. Replacement thermistors are inexpensive and plug in. Match the part number from the parts list for your model.

Switch off power at the breaker before opening either unit. Capacitors in the outdoor unit hold a charge for several minutes after power is cut.

When to call a technician

Sensor swaps are a doable DIY job on most units. Call a technician if the sensor tests good and the code persists, because that points at the control board.

Which Heil units show PF

This page applies to Heil DLCSRA / DLCSRB / DLCLRA outdoor with DLFSHA / DLFSFA indoor (2015 and later) and DLC4 / DLF4 (2013 to 2015) units on the DLC4 / DLF4 series, 2013 to 2015 (Gree-built). Heil's own documentation lists PF as "Drive board ambient temperature sensor error", the same definition used across the Gree platform it is built on. If your unit shows a code with a different shape (for example a four-character code, or a plain number), it is from a different table; use the lookup with your exact code.

Where Heil shows this code

DLC4 / DLF4 series, 2013 to 2015 (Gree-built): The code shows on the indoor unit's display in place of the temperature. If the display is off, press the Light button on the remote. Some models also count out the code as indicator blinks. E codes are system protections and faults, F codes are mostly sensor faults, H codes are outdoor and compressor protections, U codes are motor and valve faults, and P codes are power-supply faults.

Other Heil codes

Same part of the system as PF:

All Heil error codes

PF on other brands

The same characters do not always mean the same thing. Check the brand on your unit.

Questions people ask

Can I reset a Heil PF code myself?

Yes. Turn the system off at the breaker for five minutes, then restart it. If PF comes back, the fault is real and needs the checks above.

Is it safe to keep running a Heil showing PF?

The unit will usually refuse to run, or run with reduced output, until the fault is cleared. Repeated resets do not fix anything and can mask a problem that is getting worse.

Do I need a technician for Heil PF?

Work through the checks below first; they resolve most cases. If they do not, the repair itself may need a technician. Sensor swaps are a doable DIY job on most units. Call a technician if the sensor tests good and the code persists, because that points at the control board.

Sources

  • ICP DLCSRA Outdoor Unit Single Zone Ductless Service Manual 32808000801 (error code table)
  • ICP ductless installation instructions IM-KSAIC04-04 (DLCPRA / DLCSRB / DLCERB / DLCLRA error codes)
  • ICP R-410A Ductless Split System Service Manual 421 01 9204 00 (DLC4 / DLF4, 2013)

Updated September 2026. Codes and definitions vary by model year. If your manual disagrees with this page, your manual wins. Send a correction.